Wadi LH IP 65

Product group P1

Control cabinet heatings, Thermostat controlled heaters, Lm-therm GmbH, Wadi-LH IP 65
Connection leads (AL)

Technical Details

• Protection class I (ground wire) - protection type IP 65
• Temperature setting:
   ON 35 °C - OFF 65 °C (operating temperature of
   heating system itself)
   Anti-freeze: ON < 10°C - OFF 40°C
• Connection
   Connecting leads (AL) 0.5 m, 3 x 0.75 mm² PVC
   –> Other lengths upon request
• Mounting position: horizontal
• Fastening
   Snap fitting for 35 mm DIN rail
   –> Special versions upon request



Order data

Voltage Power rating Weight Order-No. AL
115 V AC 250 W 1600 g 115250WLAL0
230 V AC 250 W 1600 g 230250WLAL0
400 V AC 250 W 1600 g 400250WLAL0
440 V AC 250 W 1600 g 440250WLAL0
500 V AC 250 W 1600 g 500250WLAL0
230 V AC 380 W 1600 g 230380WLAL0
400 V AC 380 W 1600 g 400380WLAL0
500 V AC 340 W 1600 g 500340WLAL0


Dimensional drawing Wadi-LH IP 65
Wiring diagramm
Dimensioned drawing

Details

- Slight surface temperature by the use of an integrated thermostat

- No additional thermostat necessary

- Tamper-proof

- Special temperature settings selectable